Skip to content
Sign in
CVE-2020-5807Not scoredCWE-755

CVE-2020-5807: Rockwellautomation Rockwell FactoryTalk Diagnostics vulnerability

Rockwellautomation · Rockwell FactoryTalk Diagnostics

Affected: Rockwellautomation Rockwell FactoryTalk Diagnostics · Exploitation: likely to be exploited (10% or more)

Not in CyberSIXT coverage yet: no article names this CVE. This page shows the public record.

39.3%probability of exploitation in the next 30 days
98th percentile
050100

Higher than 98% of scored CVEs

Not scored yet. The CVE record carries no CVSS score.

DescriptionCVE.org

An unauthenticated remote attacker can send data to RsvcHost.exe listening on TCP port 5241 to add entries in the FactoryTalk Diagnostics event log. The attacker can specify long fields in the log entry, which can cause an unhandled exception in wcscpy_s() if a local user opens FactoryTalk Diagnostics Viewer (FTDiagViewer.exe) to view the log entry. Observed in FactoryTalk Diagnostics 6.11. All versions of FactoryTalk Diagnostics are affected.

Affected products1

From the CVE record. A product or version that is not listed is unknown, not unaffected.

  • Rockwell FactoryTalk DiagnosticsAll versions of FactoryTalk Diagnostics

On the Atlas

Every published CVE is on the CyberSIXT Atlas, grouped by weakness, vendor and month.

Open the Atlas
Exploitation
Likely to be exploited (10% or more). EPSS gives it a 10% or higher chance of exploitation in the next 30 days.
CISA KEV
Not listed
Public check
No public nuclei template
Published
December 2020

CoverageNo articles yet

No CyberSIXT article names CVE-2020-5807 yet, so there is no coverage timeline, action brief or change log for it. Everything on this page comes from the public CVE record, CISA KEV, EPSS and the nuclei template index. Search the archive or see the CVEs in the news.

References

Updated AboutDevelopersSign in