Skip to content
Connect AISign inSign up free
CVE-2021-271967.5HighCWE-20

CVE-2021-27196: Specially Crafted IEC 61850 Protocol Sequence Vulnerability

Hitachienergy · Relion 670 Firmware

Affected: Hitachienergy Relion 670 Firmware · Exploitation: possible (1 to 10%)

Not in CyberSIXT coverage yet: no article names this CVE. This page shows the public record.

1.6%probability of exploitation in the next 30 days
75th percentile
050100

Higher than 75% of scored CVEs

7.5HighCVSS 3.1
LowHigh

DescriptionCVE.org

Improper Input Validation vulnerability in Hitachi ABB Power Grids Relion 670 Series, Relion 670/650 Series, Relion 670/650/SAM600-IO, Relion 650, REB500, RTU500 Series, FOX615 (TEGO1), MSM, GMS600, PWC600 allows an attacker with access to the IEC 61850 network with knowledge of how to reproduce the attack, as well as the IP addresses of the different IEC 61850 access points (of IEDs/products), to force the device to reboot, which renders the device inoperable for approximately 60 seconds. This vulnerability affects only products with IEC 61850 interfaces. This issue affects: Hitachi ABB Power Grids Relion 670 Series 1.1; 1.2.3 versions prior to 1.2.3.20; 2.0 versions prior to 2.0.0.13; 2.1; 2.2.2 versions prior to 2.2.2.3; 2.2.3 versions prior to 2.2.3.2. Hitachi ABB Power Grids Relion 670/650 Series 2.2.0 versions prior to 2.2.0.13. Hitachi ABB Power Grids Relion 670/650/SAM600-IO 2.2.1 versions prior to 2.2.1.6. Hitachi ABB Power Grids Relion 650 1.1; 1.2; 1.3 versions prior to 1.3.0.7. Hitachi ABB Power Grids REB500 7.3; 7.4; 7.5; 7.6; 8.2; 8.3. Hitachi ABB Power Grids RTU500 Series 7.x version 7.x and prior versions; 8.x version 8.x and prior versions; 9.x version 9.x and prior versions; 10.x version 10.x and prior versions; 11.x version 11.x and prior versions; 12.x version 12.x and prior versions. Hitachi ABB Power Grids FOX615 (TEGO1) R1D02 version R1D02 and prior versions. Hitachi ABB Power Grids MSM 2.1.0 versions prior to 2.1.0. Hitachi ABB Power Grids GMS600 1.3.0 version 1.3.0 and prior versions. Hitachi ABB Power Grids PWC600 1.0 versions prior to 1.0.1.4; 1.1 versions prior to 1.1.0.1.

On the Atlas

Every published CVE is on the CyberSIXT Atlas, grouped by weakness, vendor and month.

Open the Atlas
Exploitation
Possible (1 to 10%). EPSS between 1% and 10%.
CISA KEV
Not listed
Public check
No public nuclei template
Published
June 2021

CoverageNo articles yet

No CyberSIXT article names CVE-2021-27196 yet, so there is no coverage timeline, action brief or change log for it. Everything on this page comes from the public CVE record, CISA KEV, EPSS and the nuclei template index. Search the archive or see the CVEs in the news.

References