Skip to content
Sign in
CVE-2019-6572Not scoredCWE-200

CVE-2019-6572: Siemens AG SIMATIC HMI Comfort Panels 4" - 22" vulnerability

Siemens AG · SIMATIC HMI Comfort Panels 4" - 22"

Affected: Siemens AG SIMATIC HMI Comfort Panels 4" - 22" · Exploitation: possible (1 to 10%)

Not in CyberSIXT coverage yet: no article names this CVE. This page shows the public record.

2.7%probability of exploitation in the next 30 days
86th percentile
050100

Higher than 86% of scored CVEs

Not scored yet. The CVE record carries no CVSS score.

DescriptionCVE.org

A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15.1 Update 1), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15.1 Update 1), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Professional (All versions < V15.1 Update 1), SIMATIC WinCC (TIA Portal) (All versions < V15.1 Update 1), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). The affected device offered SNMP read and write capacities with a publicly know hardcoded community string. The security vulnerability could be exploited by an attacker with network access to the affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise confidentiality and integrity of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.

Affected products7

From the CVE record. A product or version that is not listed is unknown, not unaffected.

  • Siemens AG · SIMATIC HMI Comfort Panels 4" - 22"All versions < V15.1 Update 1
  • Siemens AG · SIMATIC HMI Comfort Outdoor Panels 7" & 15"All versions < V15.1 Update 1
  • Siemens AG · SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900FAll versions < V15.1 Update 1
  • Siemens AG · SIMATIC WinCC Runtime AdvancedAll versions < V15.1 Update 1
  • Siemens AG · SIMATIC WinCC Runtime ProfessionalAll versions < V15.1 Update 1
  • Siemens AG · SIMATIC WinCC (TIA Portal)All versions < V15.1 Update 1
  • Siemens AG · SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel)All versions

On the Atlas

Every published CVE is on the CyberSIXT Atlas, grouped by weakness, vendor and month.

Open the Atlas
Exploitation
Possible (1 to 10%). EPSS between 1% and 10%.
CISA KEV
Not listed
Public check
No public nuclei template
Published
May 2019

CoverageNo articles yet

No CyberSIXT article names CVE-2019-6572 yet, so there is no coverage timeline, action brief or change log for it. Everything on this page comes from the public CVE record, CISA KEV, EPSS and the nuclei template index. Search the archive or see the CVEs in the news.

References

Updated AboutDevelopersSign in